Facility Configuration

Category Reference
Test Site Size Optimal Size Proposal for Performance Assurance Considering Modeling, Design and Construction Environment through Chamber Performance Simulation
Modular Panel Type Galvanized Shielding Panel Assembly

Chamber Validation Standard

Category Standard Reference
Frequency Range 14kHz-18GHz
Shield Effectiveness IEEE 299, MIL-STD-285 Over 100dB at 14kHz–18GHz

Shielding Performance (IEEE299)

Category Frequency Attenuation (min)
Magnetic 10kHz More than 70dB
200kHz More than 100dB
Electric 1MHz More than 110dB
100MHz More than 110dB
500MHz More than 110dB
Plane Wave 1GHz More than 110dB
Microwave 10GHz More than 110dB
18GHz More than 100dB