Facility Configuration
Category | Reference |
---|---|
Test Site Size | Optimal Size Proposal for Performance Assurance Considering Modeling, Design and Construction Environment through Chamber Performance Simulation |
Modular Panel Type | Galvanized Shielding Panel Assembly |
Chamber Validation Standard
Category | Standard | Reference |
---|---|---|
Frequency Range | 14kHz-18GHz | |
Shield Effectiveness | IEEE 299, MIL-STD-285 | Over 100dB at 14kHz–18GHz |
Shielding Performance (IEEE299)
Category | Frequency | Attenuation (min) |
---|---|---|
Magnetic | 10kHz | More than 70dB |
200kHz | More than 100dB | |
Electric | 1MHz | More than 110dB |
100MHz | More than 110dB | |
500MHz | More than 110dB | |
Plane Wave | 1GHz | More than 110dB |
Microwave | 10GHz | More than 110dB |
18GHz | More than 100dB |